ABB ACS800: How to change the ACS800 Drive rating ID?

To change the rated value ID of ABB ACS800 frequency converter, the basic parameters of the motor need to be set first. The following are the setup steps:
Setting the basic parameters of the motor: Firstly, it is necessary to set the basic parameters of the motor, such as rated current, rated frequency, rated speed, and rated power. These parameters can usually be found on the nameplate of the motor and set according to the following parameter codes:
99.06=rated current
99.07=rated frequency
99.08=rated speed
99.09=rated power
Panel selection: Select the operation panel as LOCAL mode.
Start identification: Press the run button to start identifying the motor parameters. During the identification process, warning messages such as MOTOR STARTS and ID DON will be displayed, indicating that the identification process is in progress.
Confirmation of identification completion: When “ID DONE” appears on the display screen, it indicates that the motor parameter identification is complete.
In addition, the following points should be noted:
Before setting parameters, ensure that the control panel is in local control mode, which can be switched between the two modes by pressing LOL/REM.
Before performing ID RUN, if the parameter values (10 to 98 groups) have been modified, it is necessary to confirm that the newly set values meet specific conditions, such as minimum speed, maximum speed, maximum current, maximum torque, etc.
When performing ID RUN, press “ENTER” to confirm the selection, then press “RUN” to start ID RUN until the display screen shows “ID DONE”.